6 AWG wire size

4.115 mm · 13.302 mm²

0.162 in diameter · 1.296 Ω/km in copper · 55 A (NEC 60 °C copper)

What 6 AWG is used for

Electric ovens, hot tubs, 55-amp circuits and welder outlets.

The numbers

Diameter4.115 mm · 0.162 in
Cross-sectional area13.3018 mm²
Resistance, copper1.296 Ω/km · 0.395 Ω per 1,000 ft
Resistance, aluminium2.12 Ω/km
NEC 60 °C copper ampacity55 A

How 6 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 3 AWG has twice the copper of 6 — 26.67 mm² against 13.302 — and therefore half the resistance per metre. 1/0 AWG is twice the diameter, which is four times the area.

GaugeDiameterAreaΩ/km coppervs 6
1/08.251 mm53.475 mm²0.324.02× the area
17.348 mm42.408 mm²0.413.19× the area
26.544 mm33.631 mm²0.512.53× the area
35.827 mm26.67 mm²0.652.01× the area
45.189 mm21.151 mm²0.821.59× the area
83.264 mm8.366 mm²2.060.63× the area
102.588 mm5.261 mm²3.280.4× the area
122.053 mm3.309 mm²5.210.25× the area

Frequently asked questions

What is 6 AWG in mm?

4.115 mm in diameter (0.162 inches), with a cross-sectional area of 13.302 mm².

How many amps can 6 AWG copper carry?

55 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 6 AWG copper?

1.296 Ω per kilometre, or 0.395 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 2.12 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

How much thicker is 3 AWG than 6?

Three gauges lower is twice the cross-sectional area — 26.67 mm² against 13.302, a ratio of 2.005. That is not a coincidence: the AWG formula raises 92 to the power of (36−n)/39, and 92^(6/39) is 2.005.

The full AWG chart · Unit converters