Toolman

8 AWG wire size

3.264 mm · 8.366 mm²

0.1285 in diameter · 2.061 Ω/km in copper · 40 A (NEC 60 °C copper)

What 8 AWG is used for

40-amp circuits — ranges, larger air conditioners, EV chargers.

The numbers

Diameter3.264 mm · 0.1285 in
Cross-sectional area8.3656 mm²
Resistance, copper2.061 Ω/km · 0.628 Ω per 1,000 ft
Resistance, aluminium3.371 Ω/km
NEC 60 °C copper ampacity40 A

How 8 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 2 AWG is twice the diameter, which is four times the area.

GaugeDiameterAreaΩ/km coppervs 8
26.544 mm33.631 mm²0.514.02× the area
35.827 mm26.67 mm²0.653.19× the area
45.189 mm21.151 mm²0.822.53× the area
64.115 mm13.302 mm²1.31.59× the area
102.588 mm5.261 mm²3.280.63× the area
122.053 mm3.309 mm²5.210.4× the area
141.628 mm2.081 mm²8.280.25× the area

Frequently asked questions

What is 8 AWG in mm?

3.264 mm in diameter (0.1285 inches), with a cross-sectional area of 8.366 mm².

How many amps can 8 AWG copper carry?

40 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 8 AWG copper?

2.061 Ω per kilometre, or 0.628 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 3.37 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

Why do smaller AWG numbers mean thicker wire?

The number counts drawing operations. Wire is pulled through progressively smaller dies, and the gauge records how many passes it took — so more passes means a higher number and a thinner wire.

The full AWG chart · Unit converters