2 AWG wire size

6.544 mm · 33.631 mm²

0.2576 in diameter · 0.513 Ω/km in copper · 95 A (NEC 60 °C copper)

What 2 AWG is used for

Subpanel feeders, welding cable, marine battery leads.

The numbers

Diameter6.544 mm · 0.2576 in
Cross-sectional area33.6308 mm²
Resistance, copper0.513 Ω/km · 0.156 Ω per 1,000 ft
Resistance, aluminium0.839 Ω/km
NEC 60 °C copper ampacity95 A

How 2 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 2/0 AWG has twice the copper of 2 — 67.431 mm² against 33.631 — and therefore half the resistance per metre.

GaugeDiameterAreaΩ/km coppervs 2
4/011.684 mm107.219 mm²0.163.19× the area
3/010.405 mm85.029 mm²0.22.53× the area
2/09.266 mm67.431 mm²0.262.01× the area
1/08.251 mm53.475 mm²0.321.59× the area
17.348 mm42.408 mm²0.411.26× the area
35.827 mm26.67 mm²0.650.79× the area
45.189 mm21.151 mm²0.820.63× the area
64.115 mm13.302 mm²1.30.4× the area

Frequently asked questions

What is 2 AWG in mm?

6.544 mm in diameter (0.2576 inches), with a cross-sectional area of 33.631 mm².

How many amps can 2 AWG copper carry?

95 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 2 AWG copper?

0.513 Ω per kilometre, or 0.156 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 0.84 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

How much thicker is 2/0 AWG than 2?

Three gauges lower is twice the cross-sectional area — 67.431 mm² against 33.631, a ratio of 2.005. That is not a coincidence: the AWG formula raises 92 to the power of (36−n)/39, and 92^(6/39) is 2.005.