4/0 AWG wire size

11.684 mm · 107.219 mm²

0.46 in diameter · 0.161 Ω/km in copper · 195 A (NEC 60 °C copper)

What 4/0 AWG is used for

Service entrance conductors and the main feed into a domestic panel.

The numbers

Diameter11.684 mm · 0.46 in
Cross-sectional area107.2193 mm²
Resistance, copper0.161 Ω/km · 0.049 Ω per 1,000 ft
Resistance, aluminium0.263 Ω/km
NEC 60 °C copper ampacity195 A

How 4/0 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. Going the other way, 1/0 AWG has half the area and twice the resistance.

GaugeDiameterAreaΩ/km coppervs 4/0
3/010.405 mm85.029 mm²0.20.79× the area
2/09.266 mm67.431 mm²0.260.63× the area
1/08.251 mm53.475 mm²0.320.5× the area
17.348 mm42.408 mm²0.410.4× the area
26.544 mm33.631 mm²0.510.31× the area
35.827 mm26.67 mm²0.650.25× the area

Frequently asked questions

What is 4/0 AWG in mm?

11.684 mm in diameter (0.46 inches), with a cross-sectional area of 107.219 mm².

How many amps can 4/0 AWG copper carry?

195 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 4/0 AWG copper?

0.161 Ω per kilometre, or 0.049 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 0.26 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

Why do smaller AWG numbers mean thicker wire?

The number counts drawing operations. Wire is pulled through progressively smaller dies, and the gauge records how many passes it took — so more passes means a higher number and a thinner wire.