1/0 AWG wire size

8.251 mm · 53.475 mm²

0.3249 in diameter · 0.322 Ω/km in copper · 125 A (NEC 60 °C copper)

What 1/0 AWG is used for

Feeders, welding leads and battery cable in vehicles.

The numbers

Diameter8.251 mm · 0.3249 in
Cross-sectional area53.4751 mm²
Resistance, copper0.322 Ω/km · 0.098 Ω per 1,000 ft
Resistance, aluminium0.527 Ω/km
NEC 60 °C copper ampacity125 A

How 1/0 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 4/0 AWG has twice the copper of 1/0 — 107.219 mm² against 53.475 — and therefore half the resistance per metre. Going the other way, 3 AWG has half the area and twice the resistance.

GaugeDiameterAreaΩ/km coppervs 1/0
4/011.684 mm107.219 mm²0.162.01× the area
3/010.405 mm85.029 mm²0.21.59× the area
2/09.266 mm67.431 mm²0.261.26× the area
17.348 mm42.408 mm²0.410.79× the area
26.544 mm33.631 mm²0.510.63× the area
35.827 mm26.67 mm²0.650.5× the area
45.189 mm21.151 mm²0.820.4× the area
64.115 mm13.302 mm²1.30.25× the area

Frequently asked questions

What is 1/0 AWG in mm?

8.251 mm in diameter (0.3249 inches), with a cross-sectional area of 53.475 mm².

How many amps can 1/0 AWG copper carry?

125 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 1/0 AWG copper?

0.322 Ω per kilometre, or 0.098 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 0.53 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

How much thicker is 4/0 AWG than 1/0?

Three gauges lower is twice the cross-sectional area — 107.219 mm² against 53.475, a ratio of 2.005. That is not a coincidence: the AWG formula raises 92 to the power of (36−n)/39, and 92^(6/39) is 2.005.

The full AWG chart · Unit converters