4 AWG wire size

5.189 mm · 21.151 mm²

0.2043 in diameter · 0.815 Ω/km in copper · 70 A (NEC 60 °C copper)

What 4 AWG is used for

Ranges, subpanel feeders and heavy motor loads.

The numbers

Diameter5.189 mm · 0.2043 in
Cross-sectional area21.1506 mm²
Resistance, copper0.815 Ω/km · 0.248 Ω per 1,000 ft
Resistance, aluminium1.333 Ω/km
NEC 60 °C copper ampacity70 A

How 4 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 1 AWG has twice the copper of 4 — 42.408 mm² against 21.151 — and therefore half the resistance per metre. 3/0 AWG is twice the diameter, which is four times the area.

GaugeDiameterAreaΩ/km coppervs 4
3/010.405 mm85.029 mm²0.24.02× the area
2/09.266 mm67.431 mm²0.263.19× the area
1/08.251 mm53.475 mm²0.322.53× the area
17.348 mm42.408 mm²0.412.01× the area
26.544 mm33.631 mm²0.511.59× the area
35.827 mm26.67 mm²0.651.26× the area
64.115 mm13.302 mm²1.30.63× the area
83.264 mm8.366 mm²2.060.4× the area

Frequently asked questions

What is 4 AWG in mm?

5.189 mm in diameter (0.2043 inches), with a cross-sectional area of 21.151 mm².

How many amps can 4 AWG copper carry?

70 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 4 AWG copper?

0.815 Ω per kilometre, or 0.248 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 1.33 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

How much thicker is 1 AWG than 4?

Three gauges lower is twice the cross-sectional area — 42.408 mm² against 21.151, a ratio of 2.005. That is not a coincidence: the AWG formula raises 92 to the power of (36−n)/39, and 92^(6/39) is 2.005.