3 AWG wire size

5.827 mm · 26.67 mm²

0.2294 in diameter · 0.646 Ω/km in copper · 85 A (NEC 60 °C copper)

What 3 AWG is used for

Feeders and large motor circuits.

The numbers

Diameter5.827 mm · 0.2294 in
Cross-sectional area26.6705 mm²
Resistance, copper0.646 Ω/km · 0.197 Ω per 1,000 ft
Resistance, aluminium1.057 Ω/km
NEC 60 °C copper ampacity85 A

How 3 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 1/0 AWG has twice the copper of 3 — 53.475 mm² against 26.67 — and therefore half the resistance per metre. Going the other way, 6 AWG has half the area and twice the resistance. 4/0 AWG is twice the diameter, which is four times the area.

GaugeDiameterAreaΩ/km coppervs 3
4/011.684 mm107.219 mm²0.164.02× the area
3/010.405 mm85.029 mm²0.23.19× the area
2/09.266 mm67.431 mm²0.262.53× the area
1/08.251 mm53.475 mm²0.322.01× the area
17.348 mm42.408 mm²0.411.59× the area
26.544 mm33.631 mm²0.511.26× the area
45.189 mm21.151 mm²0.820.79× the area
64.115 mm13.302 mm²1.30.5× the area

Frequently asked questions

What is 3 AWG in mm?

5.827 mm in diameter (0.2294 inches), with a cross-sectional area of 26.67 mm².

How many amps can 3 AWG copper carry?

85 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 3 AWG copper?

0.646 Ω per kilometre, or 0.197 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 1.06 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

How much thicker is 1/0 AWG than 3?

Three gauges lower is twice the cross-sectional area — 53.475 mm² against 26.67, a ratio of 2.005. That is not a coincidence: the AWG formula raises 92 to the power of (36−n)/39, and 92^(6/39) is 2.005.