1 AWG wire size

7.348 mm · 42.408 mm²

0.2893 in diameter · 0.407 Ω/km in copper · 110 A (NEC 60 °C copper)

What 1 AWG is used for

Feeders and heavy battery cable.

The numbers

Diameter7.348 mm · 0.2893 in
Cross-sectional area42.4077 mm²
Resistance, copper0.407 Ω/km · 0.124 Ω per 1,000 ft
Resistance, aluminium0.665 Ω/km
NEC 60 °C copper ampacity110 A

How 1 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 3/0 AWG has twice the copper of 1 — 85.029 mm² against 42.408 — and therefore half the resistance per metre. Going the other way, 4 AWG has half the area and twice the resistance.

GaugeDiameterAreaΩ/km coppervs 1
4/011.684 mm107.219 mm²0.162.53× the area
3/010.405 mm85.029 mm²0.22.01× the area
2/09.266 mm67.431 mm²0.261.59× the area
1/08.251 mm53.475 mm²0.321.26× the area
26.544 mm33.631 mm²0.510.79× the area
35.827 mm26.67 mm²0.650.63× the area
45.189 mm21.151 mm²0.820.5× the area
64.115 mm13.302 mm²1.30.31× the area

Frequently asked questions

What is 1 AWG in mm?

7.348 mm in diameter (0.2893 inches), with a cross-sectional area of 42.408 mm².

How many amps can 1 AWG copper carry?

110 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 1 AWG copper?

0.407 Ω per kilometre, or 0.124 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 0.66 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

How much thicker is 3/0 AWG than 1?

Three gauges lower is twice the cross-sectional area — 85.029 mm² against 42.408, a ratio of 2.005. That is not a coincidence: the AWG formula raises 92 to the power of (36−n)/39, and 92^(6/39) is 2.005.