10 AWG wire size

2.588 mm · 5.261 mm²

0.1019 in diameter · 3.277 Ω/km in copper · 30 A (NEC 60 °C copper)

What 10 AWG is used for

30-amp circuits: electric dryers, water heaters, window air conditioners.

The numbers

Diameter2.588 mm · 0.1019 in
Cross-sectional area5.2612 mm²
Resistance, copper3.277 Ω/km · 0.999 Ω per 1,000 ft
Resistance, aluminium5.36 Ω/km
NEC 60 °C copper ampacity30 A

How 10 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 4 AWG is twice the diameter, which is four times the area.

GaugeDiameterAreaΩ/km coppervs 10
45.189 mm21.151 mm²0.824.02× the area
64.115 mm13.302 mm²1.32.53× the area
83.264 mm8.366 mm²2.061.59× the area
122.053 mm3.309 mm²5.210.63× the area
141.628 mm2.081 mm²8.280.4× the area
161.291 mm1.309 mm²13.170.25× the area

Frequently asked questions

What is 10 AWG in mm?

2.588 mm in diameter (0.1019 inches), with a cross-sectional area of 5.261 mm².

How many amps can 10 AWG copper carry?

30 A under the NEC 60 °C copper column, which is the figure that sets the breaker on an ordinary branch circuit. This is a starting point and not a permission: the real limit depends on insulation rating, ambient temperature, how many conductors share the run, and your local code.

What is the resistance of 10 AWG copper?

3.277 Ω per kilometre, or 0.999 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 5.36 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

Why do smaller AWG numbers mean thicker wire?

The number counts drawing operations. Wire is pulled through progressively smaller dies, and the gauge records how many passes it took — so more passes means a higher number and a thinner wire.