8 AWG vs 12 AWG

8 AWG12 AWG
Diameter3.264 mm2.053 mm
Cross-section8.37 mm²3.31 mm²
Resistance (copper)2.06 Ω/km5.21 Ω/km
NEC 60 °C ampacity40 A20 A

Which is thicker

8 AWG has 2.53× the copper of 12 AWG in cross-section, and carries current with 60% less resistance per metre. AWG numbers run backwards because the scale counts drawing passes: more passes, thinner wire, higher number.

Voltage lost over a run at 20 A

One-way run8 AWG12 AWG
10 m (33 ft)0.82 V (0.7%)2.08 V (1.7%)
20 m (66 ft)1.65 V (1.4%)4.17 V (3.5%) over 3%
30 m (98 ft)2.47 V (2.1%)6.25 V (5.2%) over 3%
50 m (164 ft)4.12 V (3.4%) over 3%10.42 V (8.7%) over 3%

Figures are for a 120 V supply and count both conductors, because the current returns along the neutral. 12 AWG stays inside 3% out to about 17 m; 8 AWG reaches 43 m. That gap is the usual reason to upsize a wire the ampacity table already allows.

What each is rated to carry

On the NEC 310.16 60 °C column, 8 AWG copper is rated 40 A and 12 AWG is rated 20 A. Those figures set the breaker, and they are not the whole story: insulation type, ambient temperature, how many conductors share a conduit and your local code all move them. Circuit design is an electrician's call, not a table's.

Frequently asked questions

What is the difference between 8 AWG and 12 AWG?

8 AWG is the thicker wire: 3.264 mm across against 2.053 mm, with 2.53× the cross-section. Thicker copper means lower resistance — 2.06 Ω/km against 5.21 Ω/km — so less voltage is lost along a run.

Can I use 8 AWG instead of 12 AWG?

Going thicker is electrically safe — 8 AWG has less resistance and runs cooler than 12 AWG at the same current. The practical limits are cost, stiffness and whether it fits the terminals. Going the other way, to thinner wire, is the direction that needs the ampacity table and an electrician.

How far can 12 AWG run at 20 A?

About 17 m (56 ft) before the drop reaches 3% of a 120 V supply. 8 AWG reaches 43 m (141 ft) at the same current. The 3% figure is the informational note in NEC 210.19, not a hard rule, but it is the number most designs work to.