20 AWG wire size

0.812 mm · 0.518 mm²

0.032 in diameter · 33.306 Ω/km in copper

What 20 AWG is used for

Signal wiring, small transformers and hobby electronics.

The numbers

Diameter0.812 mm · 0.032 in
Cross-sectional area0.5176 mm²
Resistance, copper33.306 Ω/km · 10.152 Ω per 1,000 ft
Resistance, aluminium54.48 Ω/km
NEC 60 °C copper ampacityoutside the common building-wire range

How 20 compares

The gauge scale is geometric, so the useful comparisons are ratios rather than differences. 14 AWG is twice the diameter, which is four times the area.

GaugeDiameterAreaΩ/km coppervs 20
141.628 mm2.081 mm²8.284.02× the area
161.291 mm1.309 mm²13.172.53× the area
181.024 mm0.823 mm²20.951.59× the area
220.644 mm0.326 mm²52.960.63× the area
240.511 mm0.205 mm²84.210.4× the area
260.405 mm0.129 mm²133.90.25× the area

Frequently asked questions

What is 20 AWG in mm?

0.812 mm in diameter (0.032 inches), with a cross-sectional area of 0.518 mm².

Is 20 AWG used for power wiring?

Not for building circuits. It is a signal and low-current gauge — thinner than anything a domestic branch circuit uses.

What is the resistance of 20 AWG copper?

33.306 Ω per kilometre, or 10.152 Ω per 1,000 feet, for annealed copper at 20 °C. The same gauge in aluminium is about 54.48 Ω/km — 1.64 times higher, which is why aluminium wiring is sized larger for the same load.

Why do smaller AWG numbers mean thicker wire?

The number counts drawing operations. Wire is pulled through progressively smaller dies, and the gauge records how many passes it took — so more passes means a higher number and a thinner wire.